All qualifications and part qualifications registered on the National Qualifications Framework are public property. Thus the only payment that can be made for them is for service and reproduction. It is illegal to sell this material for profit. If the material is reproduced or quoted, the South African Qualifications Authority (SAQA) should be acknowledged as the source. |
SOUTH AFRICAN QUALIFICATIONS AUTHORITY |
REGISTERED UNIT STANDARD THAT HAS PASSED THE END DATE: |
Commission air-conditioning and ventilation systems |
SAQA US ID | UNIT STANDARD TITLE | |||
116375 | Commission air-conditioning and ventilation systems | |||
ORIGINATOR | ||||
SGB Air-conditioning Refrigeration and Ventilation | ||||
PRIMARY OR DELEGATED QUALITY ASSURANCE FUNCTIONARY | ||||
- | ||||
FIELD | SUBFIELD | |||
Field 06 - Manufacturing, Engineering and Technology | Manufacturing and Assembly | |||
ABET BAND | UNIT STANDARD TYPE | PRE-2009 NQF LEVEL | NQF LEVEL | CREDITS |
Undefined | Regular | Level 4 | NQF Level 04 | 8 |
REGISTRATION STATUS | REGISTRATION START DATE | REGISTRATION END DATE | SAQA DECISION NUMBER | |
Passed the End Date - Status was "Reregistered" |
2018-07-01 | 2023-06-30 | SAQA 06120/18 | |
LAST DATE FOR ENROLMENT | LAST DATE FOR ACHIEVEMENT | |||
2024-06-30 | 2027-06-30 |
In all of the tables in this document, both the pre-2009 NQF Level and the NQF Level is shown. In the text (purpose statements, qualification rules, etc), any references to NQF Levels are to the pre-2009 levels unless specifically stated otherwise. |
This unit standard replaces: |
US ID | Unit Standard Title | Pre-2009 NQF Level | NQF Level | Credits | Replacement Status |
9522 | Commission air-conditioning and ventilation systems | Level 4 | NQF Level 04 | 8 |
PURPOSE OF THE UNIT STANDARD |
Commission and put into operation of an air-conditioning or ventilation plant. |
LEARNING ASSUMED TO BE IN PLACE AND RECOGNITION OF PRIOR LEARNING |
UNIT STANDARD RANGE |
All air and air-water systems as applied to:
Constant volume (including full outside air systems), constant volume with terminal reheat systems and variable airflow (VAV) systems including economy cycle Controls (including electronic controls): Thermostats, temperature sensors and controllers, humidistats, pressure sensors, overheating stats, pressure switches, flow switches, Control systems: Temperature, pressure and humidity control systems for air and chilled water systems. |
Specific Outcomes and Assessment Criteria: |
SPECIFIC OUTCOME 1 |
Plan and organise the commissioning of the air-conditioning plant |
ASSESSMENT CRITERIA |
ASSESSMENT CRITERION 1 |
Plans and schedules for the commissioning are drawn up in accordance with project specifications. |
ASSESSMENT CRITERION 2 |
Work activities are planned to produce the required results within the available time. |
ASSESSMENT CRITERION 3 |
The ability to determine resources required in terms of component, spares, people, finances, tools and instrumentation is demonstrated. |
ASSESSMENT CRITERION 4 |
Tools and instrumentation are checked and ensured to be functional and ready for use. |
ASSESSMENT CRITERION 5 |
The ability to liaise with others and co-ordinate resources is demonstrated. |
ASSESSMENT CRITERION 6 |
Work area is checked for hazards, all hazards are identified and corrective action is taken in line with worksite housekeeping procedures. |
ASSESSMENT CRITERION 7 |
Support personnel are utilized in line with their expertise and instructions are given which promote good working relationship and ensure effective work. |
ASSESSMENT CRITERION 8 |
Commissioning of refrigeration system or the chiller plant, if appropriate, is confirmed. |
ASSESSMENT CRITERION 9 |
Consequences of bad or inadequate planning are listed and explained. |
SPECIFIC OUTCOME 2 |
Carry out pre-start up checks. |
ASSESSMENT CRITERIA |
ASSESSMENT CRITERION 1 |
Work is carried out in accordance with work place safety requirements. |
ASSESSMENT CRITERION 2 |
Air-conditioning or ventilation system components and accessories are checked for correct installation and suitability for operation. |
ASSESSMENT CRITERION 3 |
Controls and control devices are checked to ensure that they are connected properly and operating in line with their intended use. |
ASSESSMENT CRITERION 4 |
Instrumentation and tools are used in accordance with manufacturer's instructions and correction factors are applied where necessary. |
ASSESSMENT CRITERION 5 |
Electrical systems are checked in compliance with performance and safety requirements. |
ASSESSMENT CRITERION 6 |
Consequences of not carrying out pre-start checks are listed and explained. |
SPECIFIC OUTCOME 3 |
Set plant in operation. |
ASSESSMENT CRITERIA |
ASSESSMENT CRITERION 1 |
Plant is started according to specifications or instructions. |
ASSESSMENT CRITERION 2 |
The sequence of start-up is checked and found to be in accordance with system specifications |
ASSESSMENT CRITERION 3 |
Systems are test-run, checked and adjusted to meet performance requirements. |
ASSESSMENT CRITERION 4 |
Controls are verified to ensure performance in accordance with specified requirements. |
ASSESSMENT CRITERION 5 |
Direction of rotation of fans and pumps are checked and ratings verified. |
ASSESSMENT CRITERION 6 |
Vibration and noise levels of rotating equipment are confirmed to be within specified limits. |
ASSESSMENT CRITERION 7 |
The consequence of poor workmanship is described in terms of system effectiveness, operating costs and safety. |
SPECIFIC OUTCOME 4 |
Check and verify operation of plant. |
ASSESSMENT CRITERIA |
ASSESSMENT CRITERION 1 |
Airflow and pressure measurements in ducting system are carried out in accordance with company technical guidelines. |
ASSESSMENT CRITERION 2 |
Air quantities are checked and adjusted to meet specifications. |
ASSESSMENT CRITERION 3 |
Water flows are checked and adjusted to meet specifications. |
ASSESSMENT CRITERION 4 |
Correct measuring positions are selected. |
ASSESSMENT CRITERION 5 |
Correct measuring instruments are used. |
ASSESSMENT CRITERION 6 |
Balancing of the air and water supply systems is carried out in accordance with company technical guidelines. |
ASSESSMENT CRITERION 7 |
Performance tests are carried out and data is checked and recorded as required by specified commissioning procedures. |
ASSESSMENT CRITERION RANGE |
Air and water quantities, room temperatures and humidities, motor currents and voltages, outside air volume and equipment entering and leaving conditions. |
ASSESSMENT CRITERION 8 |
The nature, extent and cause of deviations in the operation of equipment and components are assessed and corrective action taken. |
ASSESSMENT CRITERION 9 |
Care is taken that the final operating parameters of the plant are within the specified limits. |
ASSESSMENT CRITERION 10 |
Non-conformance of equipment performance with specifications is reported |
ASSESSMENT CRITERION 11 |
The work is carried out within agreed time frames. |
ASSESSMENT CRITERION 12 |
The consequences of faulty plant operation are listed and explained. |
SPECIFIC OUTCOME 5 |
Hand over plant and complete commissioning documentation. |
ASSESSMENT CRITERIA |
ASSESSMENT CRITERION 1 |
A commissioning report is prepared in accordance with applicable specifications. |
ASSESSMENT CRITERION 2 |
All observations and data are accurately recorded. |
ASSESSMENT CRITERION 3 |
The site is cleaned, tools, consumables and instrumentation is stored in accordance with good housekeeping principles. |
ASSESSMENT CRITERION 4 |
Completion of commissioning is reported to designated personnel in line with company procedures. |
ASSESSMENT CRITERION 5 |
Manuals and operating instructions are finalized. |
ASSESSMENT CRITERION 6 |
Operating personnel is trained in accordance with operating instructions. |
ASSESSMENT CRITERION 7 |
Equipment and/or plant are handed over to user. |
ASSESSMENT CRITERION 8 |
Job cards are completed in accordance with company guidelines. |
UNIT STANDARD ACCREDITATION AND MODERATION OPTIONS |
Any person wishing to be assessed against this unit standard may apply to an assessment agency, assessor or provider institution accredited by the relevant ETQA, who may appoint a moderator to be present at the assessment.
The assessor must have knowledge and experience of air-conditioning or refrigeration. |
UNIT STANDARD ESSENTIAL EMBEDDED KNOWLEDGE |
UNIT STANDARD DEVELOPMENTAL OUTCOME |
Knowledge of operation of air-conditioning system |
UNIT STANDARD LINKAGES |
N/A |
Critical Cross-field Outcomes (CCFO): |
UNIT STANDARD CCFO IDENTIFYING |
and rectifying same |
UNIT STANDARD CCFO WORKING |
UNIT STANDARD CCFO ORGANISING |
UNIT STANDARD CCFO COMMUNICATING |
Presenting oral or written reports. Training of operating personnel |
UNIT STANDARD CCFO SCIENCE |
Using instrumentation. Interpreting results and taking appropriate action
Calibrating of equipment |
UNIT STANDARD CCFO DEMONSTRATING |
Describing the consequences of sub-standard commissioning work on plant operation and operating cost |
UNIT STANDARD ASSESSOR CRITERIA |
N/A |
REREGISTRATION HISTORY |
As per the SAQA Board decision/s at that time, this unit standard was Reregistered in 2012; 2015. |
UNIT STANDARD NOTES |
This unit standard replaces unit standard 9522, "Commission air-conditioning and ventilation systems", Level 4, 8 credits.
Supplementary information: Specific requirements are contained in one or more of the following documents |
QUALIFICATIONS UTILISING THIS UNIT STANDARD: |
ID | QUALIFICATION TITLE | PRE-2009 NQF LEVEL | NQF LEVEL | STATUS | END DATE | PRIMARY OR DELEGATED QA FUNCTIONARY | |
Elective | 48966 | Further Education and Training Certificate: Air-conditioning, Refrigeration and Ventilation | Level 4 | NQF Level 04 | Passed the End Date - Status was "Reregistered" |
2009-03-12 | Was MERSETA until Last Date for Achievement |
PROVIDERS CURRENTLY ACCREDITED TO OFFER THIS UNIT STANDARD: |
This information shows the current accreditations (i.e. those not past their accreditation end dates), and is the most complete record available to SAQA as of today. Some Primary or Delegated Quality Assurance Functionaries have a lag in their recording systems for provider accreditation, in turn leading to a lag in notifying SAQA of all the providers that they have accredited to offer qualifications and unit standards, as well as any extensions to accreditation end dates. The relevant Primary or Delegated Quality Assurance Functionary should be notified if a record appears to be missing from here. |
NONE |
All qualifications and part qualifications registered on the National Qualifications Framework are public property. Thus the only payment that can be made for them is for service and reproduction. It is illegal to sell this material for profit. If the material is reproduced or quoted, the South African Qualifications Authority (SAQA) should be acknowledged as the source. |