All qualifications and part qualifications registered on the National Qualifications Framework are public property. Thus the only payment that can be made for them is for service and reproduction. It is illegal to sell this material for profit. If the material is reproduced or quoted, the South African Qualifications Authority (SAQA) should be acknowledged as the source. |
SOUTH AFRICAN QUALIFICATIONS AUTHORITY |
REGISTERED UNIT STANDARD THAT HAS PASSED THE END DATE: |
Operate on low voltage networks |
SAQA US ID | UNIT STANDARD TITLE | |||
113865 | Operate on low voltage networks | |||
ORIGINATOR | ||||
SGB Electrical Engineering & Construction | ||||
PRIMARY OR DELEGATED QUALITY ASSURANCE FUNCTIONARY | ||||
- | ||||
FIELD | SUBFIELD | |||
Field 12 - Physical Planning and Construction | Electrical Infrastructure Construction | |||
ABET BAND | UNIT STANDARD TYPE | PRE-2009 NQF LEVEL | NQF LEVEL | CREDITS |
Undefined | Regular | Level 3 | NQF Level 03 | 12 |
REGISTRATION STATUS | REGISTRATION START DATE | REGISTRATION END DATE | SAQA DECISION NUMBER | |
Passed the End Date - Status was "Reregistered" |
2007-04-03 | 2009-02-18 | SAQA 0160/05 | |
LAST DATE FOR ENROLMENT | LAST DATE FOR ACHIEVEMENT | |||
2010-02-18 | 2013-02-18 |
In all of the tables in this document, both the pre-2009 NQF Level and the NQF Level is shown. In the text (purpose statements, qualification rules, etc), any references to NQF Levels are to the pre-2009 levels unless specifically stated otherwise. |
This unit standard is replaced by: |
US ID | Unit Standard Title | Pre-2009 NQF Level | NQF Level | Credits | Replacement Status |
258959 | Operate on Low Voltage networks | Level 3 | NQF Level 03 | 12 |
PURPOSE OF THE UNIT STANDARD |
This unit standard is for persons in the Low Voltage reticulation environment
The person credited with this unit standard is capable of carrying out operating on Low Voltage networks by doing: > Switching of apparatus This unit standard will contribute to the full development of the learner within the electrical reticulation environment by providing recognition, further mobility and transportability within the field of Physical Planning and Construction. The skills, knowledge and understanding demonstrated within this unit standard are essential for social and economic transformation and upliftment within the Electrical Infrastructure and Construction environment. |
LEARNING ASSUMED TO BE IN PLACE AND RECOGNITION OF PRIOR LEARNING |
UNIT STANDARD RANGE |
Specific Outcomes and Assessment Criteria: |
SPECIFIC OUTCOME 1 |
Plan and prepare to operate on low voltage networks. |
ASSESSMENT CRITERIA |
ASSESSMENT CRITERION 1 |
1. Determine the scope of work to be carried as per work request. |
ASSESSMENT CRITERION 2 |
2. The affected customers are notified of the outage times as per job requirements. |
ASSESSMENT CRITERION 3 |
3. Plan the sequence of events in conjunction with the Work Co-ordinator and work teams where applicable. |
ASSESSMENT CRITERION 4 |
4. Ensure that the relevant personal protective equipment ,earthing gear, insulated operating sticks, applicable testing devices and keys are available and serviceable. |
ASSESSMENT CRITERION 5 |
5. Visible inspection is carried out on the apparatus to be operated on to ensure that it is in a good serviceable condition as per the manufacturer`s specifications. |
SPECIFIC OUTCOME 2 |
Switch apparatus on low voltage networks. |
ASSESSMENT CRITERIA |
ASSESSMENT CRITERION 1 |
1. The appropriate Low Voltage circuit breakers are identified, checked for irregularities, correct labelling and that safety signs are attached as per the statutory requirements or operating standards. |
ASSESSMENT CRITERION 2 |
2. Ensure that the appropriate lock out devices are in place and applied as per operating or lock out procedures. |
ASSESSMENT CRITERION 3 |
3. The applicable safety gear and personal protective equipment is selected and used in accordance with safe work procedures. |
ASSESSMENT CRITERION 4 |
4. The appropriate breakers or switches are identified, operated and locked out as per operating or lock out procedures. |
SPECIFIC OUTCOME 3 |
Isolate apparatus on low voltage networks. |
ASSESSMENT CRITERIA |
ASSESSMENT CRITERION 1 |
1. The appropriate isolators, fuses or neutral links are identified and checked for irregularities and correct safety labels and signs attached as per operating procedures. |
ASSESSMENT CRITERION 2 |
2. The applicable safety gear and personal protective equipment is selected and used in accordance with safe work procedures. |
ASSESSMENT CRITERION 3 |
3. The appropriate isolators are opened or closed and status verified according to operating procedures. |
ASSESSMENT CRITERION 4 |
4. The appropriate fuses or neutral link inserts removed where applicable according to operating procedures. |
ASSESSMENT CRITERION 5 |
5. All cubical doors are secured and locked on completion of isolation according to operating procedures. |
SPECIFIC OUTCOME 4 |
Safety test and earth apparatus on low voltage networks. |
ASSESSMENT CRITERIA |
ASSESSMENT CRITERION 1 |
1. The safety test device is selected, inspected and checked for functionality prior to earthing being carried out as per operating procedures. |
ASSESSMENT CRITERION 2 |
2. The isolated Low Voltage network is safety tested as per operating procedures. |
ASSESSMENT CRITERION 3 |
3. The applicable safety gear / personal protective equipment is selected and used in accordance with safe work procedures. |
ASSESSMENT CRITERION 4 |
4. Earthing gear is correctly selected and inspected to be in good condition as per operating procedures. |
ASSESSMENT CRITERION 5 |
5. The earthing gear is adequately applied to the apparatus / circuit as per the operating procedures. |
ASSESSMENT CRITERION 6 |
6. Statutory documents or permits are issued / completed as per work site procedures. |
SPECIFIC OUTCOME 5 |
Restore supply to low voltage networks. |
ASSESSMENT CRITERIA |
ASSESSMENT CRITERION 1 |
1. All equipment has been removed from the work site and all workers have been informed that the apparatus will be returned to service according to operating regulations. |
ASSESSMENT CRITERION 2 |
2. All earthing gear is removed from the apparatus or circuit according to operating procedures. |
ASSESSMENT CRITERION 3 |
3. The appropriate isolators are opened or closed and fuses or neutral links replaced where applicable and status verified as per operating procedure. |
ASSESSMENT CRITERION 4 |
4. Lockout devices are removed according to lockout procedures. |
ASSESSMENT CRITERION 5 |
5. The appropriate breakers or switches are identified, operated, status verified and reported where necessary as per operating procedures. |
ASSESSMENT CRITERION 6 |
6. Safety labels and warning signs are removed and cubical doors locked according to operating regulations. |
UNIT STANDARD ACCREDITATION AND MODERATION OPTIONS |
1. Anyone assessing a learner against this unit standard must be registered as an assessor with the relevant ETQA.
2. Any provider offering learning that will enable achievement of this unit standard must be accredited as a provider through the relevant ETQA. 3. Moderation of assessment will be overseen by the relevant ETQA according to the moderation guidelines in the relevant qualification and the agreed ETQA procedures. |
UNIT STANDARD ESSENTIAL EMBEDDED KNOWLEDGE |
UNIT STANDARD DEVELOPMENTAL OUTCOME |
N/A |
UNIT STANDARD LINKAGES |
N/A |
Critical Cross-field Outcomes (CCFO): |
UNIT STANDARD CCFO ORGANISING |
Organise oneself and one`s activities responsibly and effectively, with the ability to follow work instructions or procedures when working independently or in a work team to ensure safe execution of work activities. |
UNIT STANDARD CCFO COLLECTING |
Collect, evaluate, organise and critically evaluate information related to operating of apparatus on low voltage networks. |
UNIT STANDARD CCFO COMMUNICATING |
Effective use of communication methods when giving or receiving instructions and notifying customers. |
UNIT STANDARD CCFO CONTRIBUTING |
Responsible thinking and decision making with regard to safety precautions and procedures during operating process to be applied at all times. |
UNIT STANDARD ASSESSOR CRITERIA |
N/A |
UNIT STANDARD NOTES |
This unit standard has been replaced by unit standard 258959, which is "Operate on Low Voltage networks", Level 3, 12 credits.
Supplementary information: Specified requirements Legal requirements: |
QUALIFICATIONS UTILISING THIS UNIT STANDARD: |
ID | QUALIFICATION TITLE | PRE-2009 NQF LEVEL | NQF LEVEL | STATUS | END DATE | PRIMARY OR DELEGATED QA FUNCTIONARY | |
Elective | 20419 | National Certificate: Electrical Engineering | Level 3 | NQF Level 03 | Passed the End Date - Status was "Registered" |
2004-02-10 | Was EWSETA until Last Date for Achievement |
Elective | 48475 | National Certificate: Electrical Engineering | Level 3 | NQF Level 03 | Passed the End Date - Status was "Reregistered" |
2009-02-18 | Was EWSETA until Last Date for Achievement |
PROVIDERS CURRENTLY ACCREDITED TO OFFER THIS UNIT STANDARD: |
This information shows the current accreditations (i.e. those not past their accreditation end dates), and is the most complete record available to SAQA as of today. Some Primary or Delegated Quality Assurance Functionaries have a lag in their recording systems for provider accreditation, in turn leading to a lag in notifying SAQA of all the providers that they have accredited to offer qualifications and unit standards, as well as any extensions to accreditation end dates. The relevant Primary or Delegated Quality Assurance Functionary should be notified if a record appears to be missing from here. |
NONE |
All qualifications and part qualifications registered on the National Qualifications Framework are public property. Thus the only payment that can be made for them is for service and reproduction. It is illegal to sell this material for profit. If the material is reproduced or quoted, the South African Qualifications Authority (SAQA) should be acknowledged as the source. |